Trident®-S is a three phase, spring-assisted load break or fault interrupting switch. Its side-mounted handles can be positioned with a hookstick eye on top or bottom, providing the ideal mechanical advantage for either vertical or horizontal mounting.
Features and Benefits
Construction - Available compact construction with front accessible switch operators and bushings, front and back accessible switch operators and bushings, or front access to operators and rear access to bushings.
Fault Interrupting - Fault Interrupting – Three phase fault interrupting up to 16kA.
SafeVu Visible Break - Available with an innovative visible break built into the switch, which eliminates the need to remove elbows or use externally mounted components to provide a visible open.
Voltage Sensing - Available with fully encapsulated integral voltage sensing for use with voltage indication panel to determine in-phase condition or for use with a relay with up to 1% accuracy.
Self Powered Protection - G&W Electric Type VI controls are self-powered by the fully encapsulated current sensors in the Trident. Standard industry curves including fuse emulation curves for overcurrent and ground fault protection.
Automation - Available for motor automation with mounted or portable control. A variety of relays such as SEL, ABB, and GE are available with G&W Electric programming and cabinet construction. Cabinets can be ordered in a low voltage enclosure for padmount, and pedestal, wall mount or IP68 rated submersible for vault installed switchgear. Programming for automatic source transfer, protection, or LaZer custom solutions are available.
| Voltage Class (kV) | 15 | 25 | 35* |
| Max. System Voltage (kV) | 15.5‡ | 27† | 38 |
| BIL (kV) | 110 | 125 | 150 |
| Continuous Current (A) | 630§ | 630§ | 630§ |
| Load Break Current (A) | 630§ | 630§ | 630§ |
| AC Withstand, 1 min. (kV) | 35 | 60 | 70 |
| AC Withstand, Productions, 1 min. (kV) | 34 | 40 | 50 |
| DC Withstand, 15 min. | 53 | 78 | 103 |
| Momentary Current, RMS, Asym (kA) | 20** | 20 | 20 |
| Fault Close 3 Times, Asym (kA) | 20** | 20 | 20 |
| Current, Sym (kA), 1 Sec. | 12.5** | 12.5 | 12.5 |
| Fault Interrupting Current, Sym (kA) | 12.5** | 12.5 | 12.5 |
| Vacuum Interrupter Mechanical Operations | 2,000 | 2,000 | 2,000 |
| Note: | |||
| § Up to 900A available on In/Out ; Up to 800A available on non-SafeVu multiway Trident | |||
| * 35kV not applicable for Trident-SP | |||
| † Models available up to 29.3kV | |||
| ‡ Trident-S with SafeVu feature limited to 95kV BIL for 15kV | |||
| ** 16kA available upon request up to 15.5kV with 25.6kA asym. Momentary Current and Fault Close | |||
|
Submersible Switchgear Applications |
|
ATC Trident padmount (front access style) Specification |
|
Multiway padmount (air gear style) Trident Specification |
|
2-way 3 phase Trident®-S fault interrupting switch Specification |
|
2-way 3 phase-Trident with SafeVu Fault Interrupter |
|
Multiway Trident with SafeVu padmount (air gear style) Specification |
|
Multiway Trident with SafeVu Front Access Guide |
|
2-way 3 phase Trident with SafeVu Load Break |