Trident®-SR series offers extremely fast operation speeds of just 3.5 cycles for both load and fault interrupting options. Its flexible design can be configured to provide a wide range of solutions for any application, from basic remote operation, to distribution automation, or Smart Grid schemes including Automatic Transfer in under 10 cycles. Trident®-SR switches offer multiple application functionality within a same compact switch footprint.
Features and Benefits
Construction - Available compact construction with front accessible switch operators and bushings, or front access to operators and rear access to bushings.
Fault Interrupting - Three phase fault interrupting up to 12.5kA.
SafeVu Visible Break - Available with an innovative visible break built into the switch, which eliminates the need to remove elbows or use externally mounted components to provide a visible open.
Voltage Sensing - Available with fully encapsulated integral voltage sensing for use with voltage indication panel to determine in-phase condition or for use with a relay with up to 1% accuracy.
Automation - The Trident®-SR switch series was specifically designed to provide the high-speed switching required for distribution automation schemes. A variety of relays such as SEL, ABB, and GE are available with G&W Electric programming and cabinet construction. Cabinets can be ordered in a low voltage enclosure for padmount, and pedestal, wall mount or IP68 rated submersible for vault installed switchgear. Programming for protection, LaZer custom solutions, or Automatic Transfer in under 10 cycles.
| Voltage Class (kV) | 15 | 25 | 35 |
| Max. System Voltage (kV) | 15.5 | 27‡ | 38 |
| BIL (kV) 110Δ 125 150 | 110Δ | 125 | 150 |
| Continuous Current (A) | 630§ | 630§ | 630§ |
| Load Break Current (A) | 630§ | 630§ | 630§ |
| AC Withstand, 1 min. (kV) | 35 | 60 | 70 |
| AC Withstand, Productions, 1 min. (kV) | 34 | 40 | 50 |
| DC Withstand, 15 min. | 53 | 78 | 103 |
| Momentary Current, RMS, asym (kA) | 20 | 20 | 20 |
| Fault Close 3 times, asym (kA) | 20 | 20 | 20 |
| 1 second Current, sym (kA) | 12.5 | 12.5 | 12.5 |
| Fault Interrupting Current, sym (kA) | 12.5 | 12.5 | 12.5 |
| Vacuum Interrupter Mechanical Operations | 10,000 | 10,000 | 10,000 |
| Δ BIL impulse rating is 95kV when using the SafeVu feature | |||
| ‡ Up to 29.3kV Max. System Voltage available | |||
| § Up to 900A available on In/Out without SafeVu, Up to 800A available on multiway Trident without SafeVu | |||
|
Submersible Switchgear Applications |